KCD2-SR-EX2 卓峙
地区:上海 上海市
认证:
无
图文详情
产品属性
相关推荐
General specifications | ||
Signal type | Digital Input | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | ≤ 10 % | |
Rated current | ≤ 30 mA | |
Power loss | ≤ 600 mW | |
Power consumption | ≤ 600 mW | |
Input | ||
Connection | terminals 1+, 2-; 3+, 4- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection | terminals 5, 6; 7, 8 | |
Output I | signal ; relay | |
Output II | signal ; relay | |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms | |
Mechanical life | 107 switching cycles | |
Transfer characteristics | ||
Switching frequency | ≤ 10 Hz | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Low voltage | ||
Directive 2006/95/EC | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Protection degree | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Protection degree | IP20 | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with Ex-areas | ||
EC-Type Examination Certificate | BASEEFA 06 ATEX 0092 , for additional certificates see www.pepperl-fuchs.com | |
Group, category, type of protection |
![]() ![]() ![]() |
|
Statement of conformity | PF 06 CERT 0972 X | |
Group, category, type of protection, temperature class |
![]() |
|
Output I, II | ||
Contact loading | 50 V AC/2 A/cos φ > 0.7; 30 V DC/2 A resistive load | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2009, EN 60079-11:2007 , EN 60079-15:2005 , EN 61241-11:2006 | |
International approvals | ||
FM approval | ||
Control drawing | 16-533FM-12 (cFMus) | |
UL approval | ||
Control drawing | 16-533FM-12 (cULus) | |
IECEx approval | IECEx BAS 06.0025 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
KCD2-SR-EX2