KFD2-STC4-EX1.20 特价 安全栅 特别推荐

地区:上海 上海市
认证:

上海卓峙自动化设备有限公司

普通会员

全部产品 进入商铺
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
  • Signal splitter (1 input and 2 outputs)
  • Dual output 0/4 mA ... 20 mA
  • Terminal blocks with test sockets
  • Up to SIL3 acc. to IEC 61508
  •  

     

    产品阐述
    Input 0/4 mA ... 20 mA
    2 x Output 0/4 mA ... 20 mA
    General specifications
    Signal type Analog input
    Supply
    Connection Power Rail or terminals 14+, 15-
    Rated voltage 20 ... 35 V DC
    Ripple within the supply tolerance
    Power loss 1.8 W
    Power consumption 2.4 W
    Input
    Connection terminals 1+, 2-, 3 or 5-, 6+
    Input signal 0/4 ... 20 mA
    Open circuit voltage/short-circuit current terminals 1+, 3-: 22.7 V / 38 mA
    Voltage drop terminals 5, 6 : ≤ 2.4 V at 20 mA
    Input resistance terminals 2-, 3: max. 76 Ω
    terminals 1+, 3: max. 500 Ω (250 Ω load)
    Available voltage terminals 1+, 3: ≥ 16 V at 20 mA
    Output
    Connection terminals 7-, 8+,9; 10-, 11+,12
    Load 0 ... 550 Ω
    Output signal 0/4 ... 20 mA (overload > 25 mA)
    Ripple max. 50 µA rms
    Transfer characteristics
    Deviation at 20 °C (68 °F), 0/4 ... 20 mA
    ≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
    Frequency range field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)
    control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
    Settling time 200 µs
    Directive conformity
    Electromagnetic compatibility
    Directive 2004/108/EC EN 61326-1:2006
    Conformity
    Electromagnetic compatibility NE 21:2011
    Protection degree IEC 60529:2001
    Ambient conditions
    Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
    Mechanical specifications
    Protection degree IP20
    Mass approx. 200 g
    Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in) , housing type B2
    Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
    Data for application in connection with Ex-areas
    EC-Type Examination Certificate BAS 99 ATEX 7060 , for additional certificates see
    Group, category, type of protection  II (1)GD, [Ex ia] IIC, [Ex iaD], (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2]
    EC-Type Examination Certificate DMT 01 ATEX E 133
    Group, category, type of protection  I (M1) [Ex ia] I
    Statement of conformity TÜV 99 ATEX 1499 X , observe statement of conformity
    Group, category, type of protection, temperature class  II 3G Ex nA II T4 [device in zone 2]
    Directive conformity
    Directive 94/9/EC EN 60079-0:2012 , EN 60079-11:2007 , EN 60079-15:2010 , EN 61241-11:2006 , EN 50303:2000
    International approvals
    UL approval
    Control drawing 116-0173 (cULus)
    IECEx approval IECEx BAS 04.0016
    Approved for [Zone 0] [Ex ia] IIC, [Ex iaD], [Ex ia] I
    General information
    Note Both output loads must be connected to ensure complete and correct operation within the technical specification.

     

    型号/规格

    KFD2-STC4-EX1.20

    品牌/商标

    P+F