图文详情
产品属性
相关推荐
6*7331-1KF02-0AB0
SIMATIC S7-300,SM 331 模拟量输入模板,光隔离,8 路模拟量输入,13 位分辨率,电压/电流/电阻/PT100、NI100、NI1000、LG-NI1000,PTC / KTY,66 ms 模板更新时间,1 X 40 针
|
6*7331-7HF01-0AB0
SIMATIC S7-300,模拟量输入SM 331,电隔离,8 AI,14 BIT,0.052MS/通道,电流,电压,中断,诊断,20针
|
6*7331-7KB02-0AB0
SIMATIC S7-300,模拟量输入SM 331,光电隔离,2 AI,9/12/14位分辨率,U/I/热电偶/电阻,中断,诊断,20针
|
模拟量输入模块将来自过程的的模拟量信号转换为可在控制器中进行内部处理的数字量信号。
该模块具有如下特点:
|
6*7331-7KF02-0AB0 |
6*7331-7HF01-0AB0 |
6*7331-1KF02-0AB0 |
6*7331-7KB02-0AB0 |
电源电压 |
|
|
|
|
负载电压 L+ |
|
|
|
|
|
24 V |
24 V |
|
24 V |
|
√ |
√ |
|
√ |
输入电流 |
|
|
|
|
从负载电压L+消耗(空载),*大 |
200 mA |
50 mA |
|
80 mA |
从背板总线 5 V DC,*大 |
50 mA |
60 mA |
90 mA |
50 mA |
功耗 |
|
|
|
|
功耗,典型值 |
1 W |
1.5 W |
0.4 W |
1.3 W |
模拟量输入 |
|
|
|
|
模拟量输入点数 |
8 |
8 |
8 |
2 |
用于电阻测量的模拟量输入点数 |
4 |
|
8 |
1 |
电压输入时的允许输入电压(破坏限值),*大值 |
20 V;连续;75 V,*长 1 s(传号空号比 1:20) |
20 V;20 VDC 永久,75 VDC *长 1 s(占空比 1:20) |
30 V;12V 连续;30V *长 1 s |
20 V;连续;75 V,*长 1 s(传号空号比 1:20) |
电流输入时允许的输入电流(破坏*限),*大 |
40 mA |
40 mA |
40 mA |
40 mA |
输入范围(额定值),电压 |
|
|
|
|
|
X |
X |
√ |
X |
|
√ |
√ |
√ |
√ |
|
X |
√ |
X |
X |
|
√ |
√ |
√ |
√ |
|
√ |
√ |
√ |
√ |
|
√ |
X |
X |
√ |
|
√ |
X |
X |
√ |
|
√ |
√ |
√ |
√ |
|
X |
X |
√ |
X |
|
√ |
√ |
√ |
√ |
|
√ |
√ |
X |
√ |
输入范围(额定值),电流 |
|
|
|
|
|
√ |
√ |
√ |
√ |
|
√ |
|
X |
√ |
|
√ |
√ |
√ |
√ |
|
√ |
X |
X |
√ |
|
√ |
√ |
√ |
√ |
输入范围(额定值),热电偶 |
|
|
|
|
|
X |
X |
X |
|
|
√ |
X |
X |
√ |
|
√ |
X |
X |
√ |
|
√ |
X |
X |
√ |
|
X |
X |
X |
X |
|
√ |
X |
X |
√ |
|
X |
X |
X |
X |
|
X |
X |
X |
X |
|
X |
X |
X |
X |
|
X |
X |
X |
X |
|
X |
X |
X |
X |
输入范围(额定值),热电阻 |
|
|
|
|
|
X |
X |
X |
X |
|
√;标准型 |
X |
√;标准型/气候型 |
√ |
|
X |
X |
√ |
|
|
X |
|
√;标准型/气候型 |
|
|
X |
|
X |
|
|
X |
|
X |
|
|
X |
|
X |
|
|
√;标准型 |
|
√;标准型/气候型 |
√ |
|
X |
|
X |
|
|
X |
|
X |
|
|
X |
|
X |
|
输入范围(额定值),电阻 |
|
|
|
|
|
√ |
X |
X |
√ |
|
√ |
X |
X |
√ |
|
√ |
X |
√ |
√ |
|
X |
X |
√ |
X |
热电偶 (TC) |
|
|
|
|
|
E, J, K, L, N 型 |
|
|
E, J, K, L, N 型 |
|
√ |
|
|
√ |
|
√ |
|
|
√ |
|
√ |
|
|
√ |
电阻温度计 (RTD) |
|
|
|
|
|
|
|
|
|
|
Pt100(标准,气候范围),Ni100(标准,气候范围) |
|
√;Pt100 标准/空调;Ni100 标准/空调;Ni1000 标准/空调;LG-Ni1000 标准/空调 |
Pt100(标准,气候范围),Ni100(标准,气候范围) |
特性曲线线性化 |
|
|
|
|
|
√ |
|
√ |
√ |
电缆长度 |
|
|
|
|
|
200m;80mV和热电偶时50m |
200 m |
200 m;50mV时*长 50 m |
200m;80mV和热电偶时50m |
6*7331-1KF02-0AB0
西门子