KFD2-EB2.R4A.B *福(P+F),批发*供应*福(P+F),
地区:福建 厦门
认证:
无
图文详情
产品属性
相关推荐
KFD2-EB2.R4A.B *福(P F)
产品阐述 | ||
redundant supply | ||
Supply | ||
Connection | terminals 11 , 12- terminals 8 , 9- | |
Rated voltage | 20 ... 30 V DC The maximum rated operational voltage of the devices plugged onto the Power Rail must not be exceeded. | |
Power loss | ≤ 2.4 W | |
Output | ||
Power Rail feed | Output current: max. 4 A | |
Fault signal | relay output: * | |
Contact loading | 40 V DC ; 2 A | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Fusing | 5 AT | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Conformity | ||
Insulation coordination | IEC 62103 | |
Electromagnetic compatibility | NE 21 | |
Protection degree | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) | |
Mechanical specifications | ||
Protection degree | IP20 | |
M* | approx. 100 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing t*e B2 | |
Data for application in connection with Ex-areas | ||
Statement of conformity | TÜV 00 ATEX 1618 X | |
Group, category, t*e of protection, temperature cl*ification | ![]() | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2006 , EN 60079-15:2005 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0160 | |
Approved for | Cl* I, Division 2, Groups A, B, C, D; Cl* I, Zone 2, IIC | |
CSA approval | ||
Control drawing | 116-0160 | |
Approved for | Cl* I, Division 2, Groups A, B, C, D; Cl* I, Zone 2, IIC |