供应SIEMENS燃气泄漏检测仪LDU11

地区:上海 上海市
认证:

上海随心电子科技有限公司

普通会员

全部产品 进入商铺
品牌:SIEMENS 型号:LDU11

本公司*提供SIEMENS各类燃气燃烧器用配件,包括程序控制器,燃气电磁阀,燃气压力开关,燃气泄漏检测仪LDU11等,价格优势明显,欢迎来电咨询

LDU11燃气检漏控制器

品牌:SIEMENS(西门子)

产地:德国

产品介绍
The LDU11... control detects leakage of the shut-off valves on gas trains with two safety shutoff valves. During each burner cycle, the LDU control unit automatically sequences, and if a leak is detected, initiates a lockout and prevents the burner from starting up.
  • Performs leak test of the gas shut-off valves before start-up and/or immediately after burner shut-down
  • No inlet gas pressure limitations
  • Easy-to-read dial indicates progress of test program
  • Ability to eliminate or leak test the vent valve
  • Cost effective control improves system safety
  • Globally Approved ?cULus, FM, CE

The LDU11 (or control unit) is used in a gas-fired combustion system with or without a vent valve in the gas train.

Installed with one or two pressure switches mounted between the gas valves, the LDU automatically initiates gas valve proving either

  • prior to burner start-up
  • immediately after the controlled shutdown, or
  • both prior to burner start-up and immediately after shutdown

The valve leak test is completed in two stages:

  • First test phase Test1, evacuates the pressure between the gas valves to test the upstream gas shutoff valve. The pipe between the gas valves is monitored by a leak detect pressure switch for no increase in pressure.
  • Second test phase Test2, pressurizes the area between the gas valves to test the downstream safety shutoff valve. The pipe between the gas valves is monitored by the leak detect pressure switch for no decrease in pressure.

If the leak detect switch signals excessive gas pressure increase during the first test phase Test1, or decrease during the second test phase Test2, the LDU control will lockout and prevent burner start-up. The indicator dial on the front of the unit indicates the progress of the leak test. When a fault occurs, the indicator dial s*s at the time of lockout, and indicates which of the valves is leaking. In the event of a lockout, the reset button on the front of the control will light orange to indicate a fault.

Pushing the clear window in front of the indicator dial once will reset the LDU control. DO *T hold in the reset button. The LDU may also be reset with a remote button (see wiring diagram).

型号表
型号主电压Hz
LDU11.523A27AC220-240V50...60
LDU11.523A17AC100-110V50...60
技术参数
主要参数
主电压AC220V -15%...AC240V +10%
AC100V -15%...AC110V +10%
主频率50Hz &plu*n;6%
外部保险丝10A
功率
-测试3.5VA
-运行2.5VA
重量4 lbs
保护等级NEMA 1251213
环境条件
运输环境IEC 60 721-3-2
内部条件cl* 2K2
温度范围-58...+140ºF
机械条件cl* 2M2
湿度<95%
运行环境IEC 60 721-3-3
内部条件cl* 3K5
机械条件cl* 3M2
温度范围-5...+140ºF
湿度<95%
不得进水