KFD2-UFT-EX2.D 现货 特卖

地区:上海 上海市
认证:

上海卓峙自动化设备有限公司

普通会员

全部产品 进入商铺
  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Input frequency 1 mHz ... 1 kHz
  • Current output 0/4 mA ... 20 mA
  • Relay and transistor output
  • Start-up override
  • Configurable by PACTware or keypad
  • Line fault detection (LFD)
  • 产品阐述
    24 V DC
    General specifications
    Signal type Digital Input
    Supply
    Connection terminals 23+, 24- or power feed module/Power Rail
    Rated voltage 20 ... 30 V DC
    Rated current approx. 130 mA
    Power loss 2.2 W
    Power consumption 2.5 W
    Input
    Connection input I: terminals 1+, 3-
    input II: terminals 4+, 6-
    input III: terminals 13+, 14- (control input 1)
    input IV: terminals 15+, 14- (control input 2)
    Input I, II 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
    Open circuit voltage/short-circuit current 8.2 V / 10 mA
    Pulse duration min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs
    Input frequency rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
    Lead monitoring breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
    Input III, IV
    Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
    Open circuit voltage/short-circuit current 18 V / 5 mA
    Output
    Connection output I: terminals 10, 11, 12
    output II: terminals 16, 17, 18
    output III: terminals 19+, 20-
    output IV: terminals 21+, 20-
    output V: terminals 7-, 8+
    Output I, II signal , relay
    Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
    Mechanical life 5 x 107 switching cycles
    Energized/De-energized delay approx. 20 ms / approx. 20 ms
    Output III and IV signal , electronic output, passive
    Contact loading 40 V DC
    Signal level 1-signal: (external voltage) - 2.5 V max. for 10 mA or 3 V max. for 100 mA (100 mA, short-circuit proof) -2.5 V (50 mA, short-circuit/overload proof)
    0-signal: switched off (off-state current ≤ 10 µA)
    Output V analog
    Current range 0 ... 20 mA or 4 ... 20 mA
    Open loop voltage max. 24 V DC
    Load max. 650 Ω
    Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
    Programming interface
    Connection programming socket
    Interface RS 232
    Collective error message Power Rail
    Transfer characteristics
    Input I and II
    Measurement range 0.001 ... 1000 Hz
    Resolution slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
    Accuracy slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
    Measuring time frequency measurement: < 100 ms
    Influence of ambient temperature 0.003 %/K (30 ppm)
    Directive conformity
    Electromagnetic compatibility
    Directive 2004/108/EC EN 61326-1:2006
    Low voltage
    Directive 2006/95/EC EN 61010-1:2010
    Conformity
    Electromagnetic compatibility NE 21:2006
    Protection degree IEC 60529:2001
    Ambient conditions
    Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
    Mechanical specifications
    Protection degree IP20
    Mass 300 g
    Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) , housing type C3
    Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
    Data for application in connection with Ex-areas
    EC-Type Examination Certificate TÜV 99 ATEX 1471 , for additional certificates see
    Group, category, type of protection  II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ Tamb ≤ 60 °C)
    Statement of conformity TÜV 02 ATEX 1885 X
    Group, category, type of protection, temperature class  II 3G Ex nA nC IIC T4
    Output I, II
    Contact loading 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
    Directive conformity
    Directive 94/9/EC EN 60079-0:2009, EN 60079-11:2007 , EN 60079-15:2005 , EN 60079-26:2007 , EN 61241-11:2006
    International approvals
    FM approval
    Control drawing 16-538FM-12

     

    型号/规格

    KFD2-UFT-EX2.D

    品牌/商标

    P+F