Used for electric signal transmission of control or monitoring circuits for 0.6/1kV
IEC 60502-1
Conductor: Stranded annealed copper wires, Sizes: 1.5 mm2 up to 10 mm2 Insulation: Polyvinyl chloride (PVC)
Color : Black with marking numbers Filler: Non-hygroscopic material(optional)
Binding tape: Polyester (Mylar) tape (optional)
Overall Screen 1: Aluminium/polyester tape is applied over each pair metallic side down in contact with tinned copper drain wire.
Sheath: Polyvinyl chloride (PVC), Black color (other colors can be provided upn request)
Maximum conductor temperature 70oC
Circuit voltage not exceeding 600 volts
Test voltage: 3500 volts
NO. OF CORES | CONDUCTOR | THICKNESS OF INSULATION |
THICKNESS OF OUTER SHEATH |
OVERALL DIAMETER | MAXIMUM CONDUCTOR RESISTANCE (AT 20°C) | CABLE WEIGHT | ||
---|---|---|---|---|---|---|---|---|
NOMINAL CROSS- SECTIONAL AREA |
NO.& DIA. OF WIRES |
DIAMETER | ||||||
MM2 | MM | MM | MM | MM | MM | OHM/KM | KG/KM | |
2 | 1.5 | 7/0.53 | 1.59 | 0.8 | 1.8 | 12 | 12.1 | 160 |
2.5 | 7/0.67 | 2.01 | 0.8 | 1.8 | 13 | 7.41 | 190 | |
4 | 7/0.85 | 2.55 | 1 | 1.8 | 14.5 | 4.61 | 260 | |
6 | 7/1.04 | 3.12 | 1 | 1.8 | 16 | 3.08 | 320 | |
10 | 7/1.35 | 4.05 | 1 | 1.8 | 17.5 | 1.83 | 430 | |
3 | 1.5 | 7/0.53 | 1.59 | 0.8 | 1.8 | 12.5 | 12.1 | 190 |
2.5 | 7/0.67 | 2.01 | 0.8 | 1.8 | 13.5 | 7.41 | 240 | |
4 | 7/0.85 | 2.55 | 1 | 1.8 | 15.5 | 4.61 | 330 | |
6 | 7/1.04 | 3.12 | 1 | 1.8 | 17 | 3.08 | 410 | |
10 | 7/1.35 | 4.05 | 1 | 1.8 | 18.5 | 1.83 | 570 | |
4 | 1.5 | 7/0.53 | 1.59 | 0.8 | 1.8 | 13.5 | 12.1 | 230 |
2.5 | 7/0.67 | 2.01 | 0.8 | 1.8 | 14.5 | 7.41 | 290 | |
4 | 7/0.85 | 2.55 | 1 | 1.8 | 16.5 | 4.61 | 410 | |
6 | 7/1.04 | 3.12 | 1 | 1.8 | 18 | 3.08 | 520 | |
10 | 7/1.35 | 4.05 | 1 | 1.8 | 20.5 | 1.83 | 720 |